Technical FAQs

Ask a Question

ATV320 drive how do you set up your reference 1 channel so that local knob is the speed reference and the digital input is the start command. 

Issue:
ATV320 drive how do you set up your reference 1 channel so that local knob is the speed reference and the digital input is the start command. 

Product Line:
All 

Environment:
All 

Cause:
Programming setting up the local knob for speed control and using the digital input for start stop. 

Resolution:
CONF > FULL > CTL-
FR1 change from AI3 to A1U1

CHCF set to SEP
CD1 is terminal . 
 
Was this helpful?
What can we do to improve the information ?