Video: How do I program an ATV320 to use the dial of drive as speed and DI1 terminal as start and stop control?

Issue:
Programming an ATV320 to use the dial of drive as speed reference and Digital Input 1 (DI1) terminal as start/stop control

Product Line:
Altivar 320, ATV320

Environment:
All

Cause:
Programming setup

Resolution:



From main menu, enter on dial.
Scroll down to CONF and enter.
Scroll down to FULL and enter.
Scroll down to CTL and enter.
Under CTL, set CHCF to SEP.
Set FR1 to A1U1.
Set CD1 to TER.