What is the "Grid Reconnect Delay" standard for an XC680-NA?

Issue:
Grid Reconnect Delay period for XCNA inverter?

Product Line:
XCNA inverter

Environment:
Applications that use any XCNA inverter

Cause:
What is the grid reconnect delay

Resolution:
This setting is based on the utility region.  For IEEE 1547, the grid reconnect delay is 300 seconds.

Note:This only takes effect if there is a grid error, this does not apply to start/stop if there are no errors.