What are the single phase ratings for Schneider Electric LK4MU3N disconnects?

Issue:
What are the single phase ratings for Schneider Electric Non-Fused disconnects?

Product Line: 
Operating Mechanism and Disconnect Switches

Environment:
North American Products

Cause:
​Customer would like to use the LK4 non fused disconnect line on single phase voltage

Resolution:

Our LK4 non-fused devices up to 200A have the below single phase ratings (Compact units: LK4DU3CN-LK4JU3CN will have this marking on their performance label)
      1ph -Max HP rating*  
Schneider P/N Rating @120VAC @240VAC @480VAC
LK4DU3CN 30A 2 5 10
LK4GU3CN 60A 5 10 25
LK4JU3CN 100A 5 10 25
LK4JU3N 100A   10  
LK4MU3N 200A   10  
LK4QU3N 400A N/A N/A N/A
LK4SU3N 600A N/A N/A N/A
LK4TU3N 800A N/A N/A N/A
LK4UU3N 1000A N/A N/A N/A
LK4WU3N 1200A N/A N/A N/A
















*For any single phase ratings outside of the above table scope. Devices will be amperage rated only.
 