How to wire and setup 0-10vdc signal to Altivar Process Drive.

Issue:
How to wire and setup 0-10vdc signal to Altivar Process Drive.

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All products of Altivar Process Drive

Cause:
N/A

Resolution:
0-10vdc (2 lead wire)
Use terminals 10V and AI1 for positive and negative wires.

Speed Pot (3 lead wire)
Use the following terminals:
10V
AI1
COM


Setup
[Complete settings] [Input/Output] [AI/AQ]

Use AI1 and AI2. Both are defaulted as 0-10vdc from the factory


 