Technical FAQs

Ask a Question

How to operate ATV320 with preset speeds.

Issue:
How to operate ATV320 with preset speeds.

Product Line:
ATV320, Altivar 320

Environment:
All

Cause:
N/A

Resolution:
Preset speed function can be assigned two ways to Altivar 320. 
1) Logic inputs  
2) Communication networks
 
1)Through Logic inputs
 
To assign preset speeds to altivar range of drives follow below path while operating JOG dial.
 
RDY--> CONF --> FULL --> Fun [Application Function]-->PSS- [Preset Speeds] -->PS2 [2 Preset speeds] = DIx. Here x refers to the available 
logic inputs number.
 
When this particular DIx is ON, SP2 (preset speed 2) reference will be considered.
 
Similarly, PS4, PS8 and PS16 can also be assigned to DIx to activate 4 preset speeds, 8 preset speeds and 16 preset speeds 
operation respectively.
 
2)Through communication networks
 
RDY-->CtL [Command Menu]-->LAC [Access Level]] = L3 [Level 3]
                                                                      
Assign any one bit from bit 11th to 15th of control word of particular communication network on which ATV320 is being used to 
preset Speeds (PS2, PS4, PS8 or PS16). Communication network could be one out of Modbus, CANOpen, DeviceNet or Profibus.
When assigned bit of control word is HIGH, corresponding preset speed function (PS2, PS4, PS* or PS16) will be activated and 
accordingly SP2 to SP16 will come into effect.

Please refer to page 180 of manual below for truth table of preset speeds on ATV320.
Was this helpful?
What can we do to improve the information ?