​Is there an adapter or mounting kit available, to allow a LA36400, LH36400, LDA, LGA, LJA, or LLA 400A breaker to be able to installed on the narrow side of a HCM,HCP,HCW, or HCRU panelboard?

Issue:
Is there an adapter  or mounting kit available to allow a powerpact or legacy L frame 400A breaker to be able to be installed on the narrow side of an I-line panel?

Product Line:
Panel, panelboard

Environment:
I-line panel, HCM, HCP, HCW, HCRU

Cause:
Mounting a branch breaker in an I-line panel larger than 250A on the narrow side.

Resolution:
No. Circuit breakers larger than 250A can only be installed on the wide side of an I-line panel, or on a single row I-line panel like the HCP-SU.
 