How many TeSys T controllers can we daisy chain out to?

Product Line:
TeSys T Motor Management System

Resolution: 
As of the April 2016 Modbus TCP / EtherNet IP user manual we state that we can install up to a maximum of 16 LTMR devices on a daisy chain network, to avoid material damage and a decrease in performance.