How do you set up an auto manual or HOA function on the ATV61 and ATV71 drives?

Issue:
How do you set up an auto manual or HOA function on the ATV61 and ATV71 drives?

Product Line:
ATV61 and ATV71

Environment:
All

Cause:
HOA is wired so that LI3 will go high for hand control via a speed pot and low for 4 to 20mA speed control via a transducer.

Resolution:

basic programming menu 1.6 drives menu
ref 1 is AI2 (4 to 20mA)
profile is not separate
ref 2 switching is channel 1 active
ref 2 channel is no

Menu 1.7 
ref 1 B switching is LI3 ( when this input is low the drive will follow the AI2 input and when its high the drive will follow the AI1 input)
ref 1 B channel is AI1

Menu 1.9
Turn off force to local and reference if assigned. 

 