How do you set up the ATV312 for auto manual control?

Issue:
How do you set up the ATV312 for auto manual control?

Product Line:
ATV312

Environment:
All 

Cause:
Wants to set up an 3 position switch for HOA control. 


Resolution:
Programming
CTL menu 
Fr1 is Ai1
Fr2 is AI3
RFC is LI3

you will need to also turn off preset speeds
FUN menu
PSS
PS4 set to no
PS2 set to no. 