Can a P Frame breaker with a Spring Charge Motor be installed in an I-Line panelboard?

Answer
Issue:
Can a P Frame breaker with a Spring Charge Motor be installed in an I-Line panelboard?

Product Line:
I Line Panelboard

Environment:
Accessory

Cause:
Installation clarification


Resolution:
Yes, in I-Line panels that will accept P Frame breakers. However, the Spring Charge Motor mandates use of a 4 piece trim with  NO door, since a door will not close over a motor operator.