How do you set up an external input with an active low to trigger an external fault on an Altivar Process Drive?

Issue:
How do you set up an external input with an active low to trigger an external fault on an Altivar Process Drive?

Product Line:
Altivar 930 and Altivar 630 drive

Environment:
All 

Cause:
Wants to turn off a digital input and have the drive trigger an external fault. 

Resolution:
Programming
Complete Settings
Menu 5
Error/Warning handling enter
External Error enter
Ex error assign enter and choose DI1 thru DI6 Low  (you must scroll all the way down to the bottom of the selection menu.)
set the external fault as DI1 Low