Technical FAQs

Ask a Question

​How to set up custom display on the ATV61 and ATV71 drives to show speed as a percent up to 100 percent?

Issue:
​How to set up custom display on the ATV61 and ATV71 drives to show speed as a percent up to 100 percent?

Product Line:
ATV61 and ATV71

Environment:
All 

Cause:
Wants to view the motor speed as a % not in hz. 

Resolution:

1st  Main menu access level is set to Expert
Main menu goto menu 7 Display
User parameters 7.1
Parameter selection
Monitoring  1.2
Choose Output Frequency by putting a check mark beside it. uncheck any others that area not used.
ESC twice back to menu menu 7.1 and now choose Customized selection
Now choose Output Frequency
Setup as follows
User Name Blank
Unit = %
Mulitplier = 100
Divisor = 60
 
ESC ESC ESC ESC back to the main menu again
 
Now choose Menu 6 monitoring config
Choose Monitor screen type 6.2
Choose Digital
ESC back out once to Menu 6.2
Now choose parameter selection
Now  put a check mark beside the Output frequency box and uncheck any other boxes that are not needed.  If you want to leave the freq reference on the screen you can leave its box checked.

Now ESC all the way back to the display that is showing your speed as a % now. 
 
Was this helpful?
What can we do to improve the information ?