What would cause the ATV630 drive to have a surging motor when the drive is running in auto mode?

Issue:
What would cause the ATV630 drive to have a surging motor when the drive is running in auto mode?.

Product Line:
ATV630

Environment:
All

Cause:
Analog input was getting interference noise and analog input was oscillation up and down. 

Resolution:
Customer was experiencing noise on his line causing motor/drive fluctuations. Had customer activate filter for AI2F. Set to 5 seconds.