What is the inrush for an EX112T212H?

Issue:
What is the inrush for an EX112T212H?

Product Line:
Low voltage Transformer

Environment:
EX transformers

Cause:
performance features

Resolution:
The inrush of an EX112T212H is 5.8 times the Full Load Amperage (FLA) of the Primary. The Primary FLA (at 208V) is 312A.  312A x 5.8 = an Inrush of 1,809A



 