Can the ATV320 be programmed using an external 24Vdc source?

Issue:
Customer wants to power the ATV320 with external 24Vdc so that it can be programmed.

Product line:
Altivar 320, ATV320

Environment:
all

Cause:
n/a

Resolution:
Yes, an external 24Vdc can be provided to the ATV320 drive in order to power up the display and program.  Connect it to terminals +24 and 0V.

 