Video: How can you turn off the flashing red caution LED on the ATV630 and ATV930 process drives?

Issue:
How can you turn off the flashing red caution LED on the ATV630 and ATV930 process drives?

Product Line:
Altivar ATV630 and ATV930

Environment:
All 

Cause:
There is a default alarm set in the warnings group for Analog input AI1 AI2 and AI3 2-20 warning that have to be turned off. 

Resolution:



Main menu go to the complete settings enter
Error Warning Handling enter
Warnings Group Configuration enter
Warn group 1 definition enter
Now uncheck AI1 AI2 and AI3  4- 20mA warning boxes.
Now the Red Flashing warning light will go out. 
 