Technical FAQs

Ask a Question

What is the torque specification for the I-line II busway flanged ends rated 800 - 5000A ?

Issue:
What is the torque specification for the I-line II  busway flanged ends rated 800 - 5000A ?   

Product Line:
Busway

Environment:
AF2330G10FEB and AF2530G10FEB

Cause:
installation

Resolution:
For the FEB type flanged ends, it is 60 - 80 lb-fts for torque values.
Was this helpful?
What can we do to improve the information ?