Issue:
How is the OPR (Output Power) function scaled on the analog output of the ATV61 and ATV71 series drives?

Product Line:
ATV61 and ATV71 series drives.

Environment:
All models, All serial numbers

Cause:
Clarification needed by customer.

Resolution:
The output power (OPR) function is scaled between 0 and 2.5X the NPR (Rated motor power) setting under menu 1.1, Simply Start.   This parameter should be set to match the horsepower or KW rating of your motor in order for the output scaling to be accurate.
 