How do you add the Fast Device Replacement or FDR name on the ATV32 drive with the optional ethernet card installed?

Issue:
How do you add the Fast Device Replacement or FDR name on the ATV32 drive with the optional ethernet card installed?

Product Line:
Altivar ATV32

Environment:
All 

Cause:
Wants to add a FDR name to the Drive 

Resolution:
You can access the FDR device name two ways.The free Somove software or on the drive direct if you have the optional VW3A1101 HMI.

 
1.) Somove software using the Ethernet cable or optional TCSMCNAM3M002P cable under the parameters tab you will see FDR.
Click on the faulty device replacement
Enable the FDR by checking the box
Add your FDR IP address
Add your Device name at the bottom.
or
 
2.) If you have the remote graphic HMI VW3A1101 + the remote bezel VW3A1102 or the optional RJ45 adaptor with cable (VW3A1104R10)
 
You can then find the PAn parameter in the ATV32 programming settings under Bluetooth settings.
COM- [COMMUNICATION] (continued)
btH- [BLUETOOTH]
pAn [Device Name]
Device name set with graphic display terminal.
Note: The length is up to 16 alphanumeric digits on the product. According to bluetooth driver, device name must not exceed 14
digits. Digits n°14 & 15 will not be displayed through bluetooth network.


 