ATV930: How to access missing menus under the Main Menu?

Issue:
Trying to program an ATV930 drive but it only provides access to the Simply Start, Dashboard, Diagnostics and My Preferences menus.

Product line:
Altivar 900, ATV930, ATV950

Environment:
all

Cause:
Factory setting on the drive is Basic Access Level.

Resolution:
Under the Main Menu, go to My Preferences > Access Level and change to Standard or Expert.
This will allow access to the Display, Complete Settings, Communication and File Management menus.