What is the Threshold at which the drive trips on SCF3 fault?

Issue:
What is the Threshold at which the drive trips on SCF3 fault?

Product Line:
ATV630, ATV650, ATV930, Altivar process

Environment:
All

Cause:
N/A

Resolution:
When the determined differential current of the three output phases is greater than
25% of the nominal inverter current, the inverter is switched off with fault message
"SCF3".