Is there a double barrel lug kit for the main lugs on a 400A main lug NQ panel?

Issue:
Is there a lug kit for an NQ, 400A main lug panel that has 2 separate barrels that will accept a 3/0 wire to 750mcm?

Product Line:
Panelboards

Environment:
NQ panelboards

Cause:
Additional wire termination

Resolution:
The standard NQ, 400A NQ panel comes with a "snowman" lug which has adjoining circles good for either (1) 1/0-750 or (2) 1/0-350. If separate barrels are needed, order the panel with sub feed lugs. It will have (2) separate barrels with each good for 1/0-750. 
 