Technical FAQs

Ask a Question

How to gear in 2 LXM28 drives in SoMachine?

Issue:
In SoMachine, how do we setup the function block GearIn_LXM28 so that the master and slave drives follow each other perfectly?

Product Line:
LXM28

Resolution:
The NUM of the GearIn_LXM28 function block should be set to 1280000 and the DENUM should be set to 8192 (2048 x 4).
This will make the perfect gear between the master and slave.
Was this helpful?
What can we do to improve the information ?