How can one setup ramp switching on the ATV630 Process drive?

Issue:
How can one setup ramp switching on the ATV630 Process drive?  

Product Line:
ATV630, Process

Environment:
All

Cause:
dual ways of ramping up to full speed.

Resolution:
Go into Complete settings under drive menu.
Go into Menu 7.31 Generic functions, Ramp switching
There is 2 ways of doing ramp switching.  One way is using frequency threshold and the other is using a logic input to switch ramp.
Ramp 2 thd (FRT) is where you would assign a frequency for second ramp to take over.
Ramp Switch Assign (RPS) is used if a logic input is preferred to be toggled for the second ramp to take over.
The first ramp is followed by acceleration and deceleration parameters.
The second ramp is followed by acceleration 2 and deceleration 2 located under Ramp switching submenu.