Technical FAQs

Ask a Question

What is the Terminal Lug Data for the EZM31000GCBT/JCBT and EZM31200GCBT/JCBT Main Devices?

Issue:
Standard Terminal Lug Data

Product Line:
EZM Metering

Environment:
EZM Main Breaker lugs

Cause:
Application

Resolution:
The Main breaker used in EZM31000GCBT, EZM31000JCBT, EZM31200GCBT and EZM31200JCBT is the PowerPact P-Frame and the standard lug is AL1200P25K and will accept as standard;
(4) 3/0-500kcmil Al/Cu wires per Phase(or per pole of the breaker) and the Main Neutral on these devices will accept as standard (4) 3/0-500kcmil Al/Cu wires (See the below attached CAD drawing).
 

Alternate lugs for the Main breakers used in the above catalog numbers:
1) Lug kit AL1200P6KU will accept (3) 350-600kcmil Al/Cu wires.(3 lugs per kit)
2) Lug kit AL1200P7KU will accept (3) 3/0 - 750kcmil(BUT the 750kcmil wire MUST be Compact Aluminum wire ONLY.(3 lugs per kit)

Alternate lugs for the Main Neutral used in the above catalog numbers:
1) Lug kit MMLK250 will accept as standard (1) 1/0-600kcmil OR (2) 1/0-250kcmil Al/Cu wires PER lug. Kit includes (3)2-Barrel lugs and neutral will accommodate ONLY 2 lugs.
 
 
Was this helpful?
What can we do to improve the information ?