Technical FAQs

Ask a Question

What is the Terminal Lug Data for the EZM11000GCBU/JCBU and EZM11200GCBU/JCBU Main Devices?

Standard Terminal Lug Data

Product Line:
EZM Metering

EZM Main Breaker lugs


The Main breaker used in EZM11000GCBU, EZM11000JCBU, EZM11200GCBU and EZM11200JCBU is the PowerPact P-Frame and the standard lug is AL1200P25K and will accept as standard;
(4) 3/0-500kcmil Al/Cu wires per Phase(or per pole of the breaker) and the Main Neutral on these devices will accept as standard (4) 3/0-500kcmil Al/Cu wires (See the below attached CAD drawing).

Alternate lugs for the Main breakers used in the above catalog numbers:
1) Lug kit AL1200P6KU will accept (3) 350-600kcmil Al/Cu wires.(3 lugs per kit)
2) Lug kit AL1200P7KU will accept (3) 3/0 - 750kcmil(BUT the 750kcmil wire MUST be Compact Aluminum wire ONLY.(3 lugs per kit)

Alternate lugs for the Main Neutral used in the above catalog numbers:
1) Lug kit MMLK250 will accept as standard (1) 1/0-600kcmil OR (2) 1/0-250kcmil Al/Cu wires PER lug. Kit includes (3)2-Barrel lugs and neutral will accommodate ONLY 2 lugs.

Additional Alternate Lugs can be used on these catalog numbers, but will REQUIRE the use of a Lug Landing Kit, catalog number EZM1200ULL. See below attached the CAD drawing showing a table of alternate lugs for use with this kit and a visual and instructions for this kit.

Was this helpful?
What can we do to improve the information ?