Technical FAQs

Ask a Question

What are errors E1300 and E1301 on the LXM32 drive?

Issue:
I am getting error E1300 and E1301 on the LXM32 drive

Product Line:
LXM32

Resolution:
E1300 means a safety STO function is activated (STO_A, STO_B)
E1301 means the levels of the inputs STO_A and STO_B were different for more than 1 second
These 2 errors are related to a bad wiring of inputs STO_A and STO_B, a bad 24V power supply or an activated emergency stop, which cuts the 24VDC from the STO inputs.
Making sure the STO inputs are getting 24VDC before powering the drive will reset these faults.
Was this helpful?
What can we do to improve the information ?