Technical FAQs

Ask a Question

Does 2SIS switchgear reduce Arc Flash requirements?


Issue:
Does 2SIS switchgear reduce Arc Flash requirements?

Product Line:
MV Switchgear

Environment:
Premset Switchgear

Cause:
Product features

Resolution:
It reduces the risks of an Arc Flash, but it does not reduce the hazard. This means the probability of an arc flash is reduced, but 2SIS does not address the available incident energy on the electrical network.
Was this helpful?
What can we do to improve the information ?