Linking GV3 with LC1D for UL Type F Applications

What piece/part is used to electrically and mechanically link the GV3P starters with the LC1D contactors to achieve the UL Type F combination SCCR ratings?

Product Line:
IEC Starters and Contactors - GIC Product

US Product

Product Specifications

No linkage part was used between the two units for SCCR testing.  Each component was mounted separately and linked only by the wiring.   