How do you orientate an 800A Main breaker HCM I line panel to make it top fed, the breaker it will be upside down?

Issue:
How do you orientate an 800A Main breaker HCM I line panel to make it top fed, the breaker it will be upside down?

Product Line:
I Line panelboard 

Environment:
Application

Cause:
Installation

Resolution:

-Rotate the entire interior of the panel.

- You will need to remove vertical Main and flip it 180 Deg for correct on/off handle orientation 

- After flipping the interior, the panel Danger & Warning labels will be upside down.  For replacements send a request to local SQ D Distributor asking them to have the Peru Plant mail out new labels 
 


 