Video: How do you set up the ATV630 process drive so HMI dial is speed reference and the terminals are start stop control?

Issue:
How do you set up the ATV630 process drive so that he HMI is the speed reference and the terminals are start stop control?

Product Line:
Altivar ATV630 and ATV930 drives

Environment:
All 

Cause:
HMI speed reference and terminal 2 wire control for starting. 

Resolution:



Programming Sequence

Main Menu 
Menu 5 complete settings
Menu 5.5 Command and references
config ref freq1= Ref Frequency via Rmt (HMI) or keypad
control mode= Separate
Command switching= Command channel 1
CMD channel 1 = terminal mode. 