​What happens when you remove a rating plug from a Micrologic Trip Unit? (Powerpact P and R, and Masterpact NT and NW)

Product Line:
Circuit Breakers

Removing the rating plug from the Micrologic Trip Unit automatically reduces the rating of the breaker to value of 40% (example: 1000A breaker becomes a 400A breaker).
This applies to the following breakers and trip units:

Circuit Breakers
Powerpact P and R
Masterpact NT and NW

Micrologic Trip Units
Standard 2.0, 3.0, 5.0
Ammeter 2.0A, 3.0A, 5.0A, 6.0A
Power 5.0P, 6.0P
Harmonic 5.0H, 6.0H