Can two different Tesys F (LC1F) contactors be interlocked mechanically?

What mechanical interlock can be used to interlock two tesys F contactors with different ratings and frame sizes?

Product Family:
Tesys F contactors, Tesys contactors, LC1F

Please see attached page for reference of the below components-
Upper Contactor Lower Contactor[1] Mechanical Interlock Kit Catalog #
LC1F185/LC1F1854 or LC1F225/LC1F2254 LC1F115/LC1F1154 or LC1F150/LC1F1504 LA9FG4F
LC1F265/LC1F2654 OR LC1F330/LC1F3304 LC1F115/LC1F1154 or LC1F150/LC1F1504 LA9FH4F
LC1F265/LC1F2654 OR LC1F330/LC1F3304 LC1F185/LC1F1854 OF LC1F225/LC1F2254 LA9FH4G
LC1F400/LC1F4004 LC1F115/LC1F1154 or LC1F150/LC1F1504 LA9FJ4F
LC1F400/LC1F4004 LC1F185/LC1F1854 OF LC1F225/LC1F2254 LA9FJ4G
LC1F400/LC1F4004 LC1F265/LC1F2654 OR LC1F330/LC1F3304 LA9FJ4H
LC1F500/LC1F5004 LC1F115/LC1F1154 or LC1F150/LC1F1504 LA9FK4F
LC1F500/LC1F5004 LC1F185/LC1F1854 OF LC1F225/LC1F2254 LA9FK4G
LC1F500/LC1F5004 LC1F265/LC1F2654 OR LC1F330/LC1F3304 LA9FK4H
LC1F500/LC1F5004 LC1F400/LC1F4004 LA9FK4J
LC1F630/LC1F6304 OR LC1F800 LC1F115/LC1F1154 or LC1F150/LC1F1504 LA9FL4F
LC1F630/LC1F6304 OR LC1F800 LC1F185/LC1F1854 OF LC1F225/LC1F2254 LA9FL4G
LC1F630/LC1F6304 OR LC1F800 LC1F265/LC1F2654 OR LC1F330/LC1F3304 LA9FL4H
LC1F630/LC1F6304 OR LC1F800 LC1F400/LC1F4004 LA9FL4J
LC1F630/LC1F6304 OR LC1F800 LC1F500/LC1F5004 LA9FL4K
[1] Vertically mounting only, Lower contactor must have equal or lesser current rating