What extra width is needed for a Back to Back installation for a Model 6 MCC transition section?

Issue:
What extra width is needed for a Back to Back installation for a Model 6 MCC transition section?

Product Line:
Model 6 Motor Control Center

Environment:
Layout

Cause:
Space allocation

Resolution:
The addtitional width needed for bussing transition section is 12" and back to back clearance needs to be 1" apart
 