What does the Modbus register 455 bit 7 monitor in the Tesys T motor management system?

Issue:
What does the Modbus register 455 bit 7 monitor in the Tesys T motor management system?

Product Line:
Motor Management Systems and Overload relays

Environment:
Tesys T

Cause:
Product Characteristics


Resolution:
Known as the 'Motor Running' bit, this bit will change state as a response to current running through the internal current transformers. The magnitude of this current must be equal or greater to 10% FLC1 setting.

 