Technical FAQs

Ask a Question

Video: How to manually trip a solid state Motor Logic™ Overload Relay

Product line:
NEMA Contactors and Starters Accessories 9065

Look on the under side of the unit for an indentation with an exposed opening that has a white plastic piece. Take a small screw driver and lift up that piece moving it to the right. You should hear a click. Check the front of the unit for the trip status indication, it should now indicate that it has been tripped. To reset the unit, press the red reset bar on the front of the overload relay device.

Was this helpful?
What can we do to improve the information ?