What is the wire bending clearances for the HCP-SU I Line interior with HC2686DB box ?

Issue:
What is the wire bending clearances for the HCP-SU , single row I Line interior with HC2686DB box ?

Product Line:
I Line Panelboards

Environment:
Installation

Cause:
Clearance

Resolution:
Gutter space for either left , or right hand breaker orientation of HCPSU interior will be 9.8 inches for Nema 1 boxes ,and 10.8" for 3R boxes
 