How do I set up my ATV12 drive to be controlled by the remote keypad (VW3A1006 or VW3A1007)?

Wants to control the VFD using the remote keypad.

Product Line:
Altivar 12, ATV12

All model numbers.  
Requires VW3A1006 or VW3A1107 remote keypad display and cable


Go to the FULL menu and the CtL submenu.
Set Fr1 to LCC.
Make sure CHCF is set to SIn.

After cycling power to the drive the remote keypad should be active for both Speed control and Start/Stop.