Do we offer a Twin QMB breaker , or Fusible switch?

Issue:
Do we offer a Twin QMB breaker , or Fusible switch?

Product Line:
QMB Panel board

Environment:
Application

Cause:
Specification

Resolution:
Yes, but only to certain amperages , ie,Twin Powerpact H frame breaker switches are tandem up to 150A  and twin fusible switches can be ordered as twins at 100A for 240V and 600V switches. A Tandem fusible switch is available for 200A using a QMJ364T, 600V rated switch, with J fuse clips 