What 2p breaker/s are to be used with a NQSFB4HJ ?.

Issue:
Breaker used with Sub-feed breaker kit

Product Line:
Panelboards

Environment:
NQ

Cause:
Installation

Resolution:
Three pole frames need to be used to fit on the back panel and just the A and C phases would be connected . Use a JDL36200 or similar. 