What can cause a CF 12 fault [Download transfer fault] on an ATV212 drive?

Download transfer fault CF12

Product Line:
ATV212, S-Flex

All models and serial numbers

The download transfer fault can be caused by parameter F807 not being set to 0.  

Parameter F807 selects the communication channel.  The two choices are 0 [RJ45] and 1 [Open style].  The default setting is 1.  If SoMove or the IPAD app is being used to configure the drive parameter F807 must be set to 0.