Can the 2 pole H and J Frame breakers be used in the J250__ enclosures?

Issue:
Product design features

Product Line:
Molded Case Circuit Breaker Enclosures

Environment:
Breakers

Cause:
Application

Resolution:
The 2-pole J frame breakers (JDL, JGL, JJL and JLL) and 2-pole HJL and HLL circuit breakers can be used in the J250__ enclosures. BUT the 2-pole HDL and HGL breakers CANNOT be used in the J250__ enclosures. The HDL and HGL breakers, use the H150__ enclosures.

 