How to resolve Scadapack Workbench Error code Expecting an integer index between [ ]


1. Variable comments with more than 60 (alphanumeric ASCII) are not allowed  (ISaGRAF 3 documentation). By removing the extra characters from some of the variables it fixes the issue.
 2. Avoid empty rungs.