Technical FAQs

Ask a Question

What is the temperature rating of the lugs on circuit breakers? (75C? 90C?)

Issue:
Are breakers rated for 90C wire?
Can you explain how to size 90 deg C conductors terminating on 75 deg C rated equipment?
How do I size wire on a breaker?

Product Line and Environment:
All Circuit Breakers

Resolution:
The wire temperature rating allowed for use in circuit breakers lugs is 75C. While it is acceptable to use 90C wire, that 90C wire must be sized as if it is 75C wire. This is according to the UL standard for circuit breakers, which is summarized as follows:
(1) Breakers rated 125A or less must be marked for use with 60C, 60/75C, or 75C only wire.
(2) For breakers rated more than 125A, the proper wire temperature rating is 75C, and the marking is optional.
(3) Wire with a higher temperature rating can be used (e.g. 90C), but the ampacity of the wire must be based on the wire temperature marked on the breaker.

Therefore, as marked on the breaker, the wire must be sized as 75C wire. Even when using 90C wire, the wire must be sized as if it is 75C wire.
Was this helpful?
What can we do to improve the information ?