Installing a ClearSCADA SSL Certificate


How do I install a ClearSCADA SSL certificate?


Follow the steps below to install an SSL certificate into ClearSCADA:

1) In the System Configuration | WebX dialog go to the 'Certificates' area and click the 'Generate' button

2) Fill out the 'Certificate Signing Request' dialog and hit the 'OK' button.  A signing request will be created.

3) Send this signing request to your certificate provider.  They will use it to generate a certificate which they will send back to you.

4) Once you receive the certificate back from the provider click the 'Install' button, browse to the certificate location and then click 'OK'.