What amperage breaker is needed for the TVS4EMA24AISWT SPD?

Issue:
What is the amperage breaker needed for the TVS4EMA24AISWT SPD?

Product Line:
Surge Protection, SPD
 
Environment:
T2, EMA, 240KA, 480Y/277V, IS SWT 3P4W
 
Cause:
Breaker requirement for TVS4EMA24AISWT?
 
Resolution:
The TVS4EMA24AISWT will require a 3P, 30A breaker.