Can a LGL36400U33X be "dialed down" to trip at 70a ?


Issue:
Change Long Time rating of breaker

Product Line:
Molded Case Circuit breakers

Environment:
Powerpact L

Cause:
Adjustment

Resolution:
No... just 125a minimum. A different 250a frame breaker can be set down to 70a . 