Both lights Flashing on RM35JA series relay

What causes both lights to flash on a RM35JA relay?

Product Line:
Control Relays - GIC Product

US Product

Product Characteristics

Typically both indicating lights will flash on these units when a dial setting is adjusted when the relay is powered up.  Setting changes must be made when the relay is powered down.  Cycle power to clear this error.