What is the lug wire range for the SN1200 neutral assembly?

Issue:
Product Features

Product Line:
Circuit Breaker Enclosure Accessory

Cause:
Wire range

Resolution:
The standard lugs provided on the neutral assembly will accept (4) #3/0 AWG - 750 kcmil CU or AL conductors, incoming and outgoing. However, the P enclosures are marked for use with 500 kcmil conductors maximum, so this would restrict the neutral conductors also to be 500 kcmil maximum. 